Beef Gap Corridor Underground Transmission Row

Electrical Safety Clearance-(IE/CEA) (Part-2)

Code: Indian Electricity Rules/ Central Electricity Authority :

Right of Way Clearance (As per GETCO Standard):

KV

Min ROW

66 KV

18 Meter

132 KV

27 Meter

220 KV

35 Meter

400KV

52 Meter (Single Circuit)

400 KV

48 Meter (Double Circuit)

Minimum clearances between Electrical Lines crossing each other:

Voltage

66 KV

132 KV

220 KV

400 KV

66 KV

2.4 Meter

3 Meter

4.5 Meter

5.4 Meter

132 KV

3 Meter

3 Meter

4.5 Meter

5.4 Meter

220 KV

4.5 Meter

4.5 Meter

4.5 Meter

5.4 Meter

400 KV

4.5 Meter

5.4 Meter

5.4 Meter

5.4 Meter

Permissible Min ground Clearance of Electrical Line:

KV

Ground Clearance

Over National Highway

66 KV

6.1 Meter

8.0 Meter

132 KV

6.1 Meter

8.6 Meter

220 KV

7.0 Meter

9.8 Meter

400KV

8.8 Meter

10.8 Meter

 Clearance for Telephone line Crossings Power Line:

KV

Clearance (Min)

66 KV

2.4 Meter

132 KV

2.7 Meter

220 KV

3.0 Meter

Vertical Clearance between Electrical Line and railway tracks.

KV

Clearance (Min)

66 KV

14 Meter

132 KV

14.6 Meter

220 KV

15.4 Meter

400 KV

17.9 Meter

Clearance from Buildings to low, medium & high voltage lines:

Voltage Description Distance
Low & Medium Voltage Flat roof, open balcony, verandah roof ,When the line passes above the building a vertical clearance from the highest point 2.5 Meter
Low & Medium Voltage Line passes adjacent to the building a horizontal clearance from the nearest point 1.2 Meter
Low & Medium Voltage Line passes above the building a vertical clearance 2.5 Meter
Low & Medium Voltage Line passes adjacent the building a Horizontal clearance 1.2 Meter
11 KV to 33 KV Line passes above or adjacent   to any building or part of a building 3.7  Meter
Above 33 KV Line passes above or adjacent   to any building or part of a building 3.7+(0.3 for every additional 33 KV )
Up to 11 KV The horizontal clearance between the nearer conductor and any part of such building 1.2 Meter
11 KV to 33 KV The horizontal clearance between the nearer conductor and any part of such building 2.0 Meter
Above 33 KV The horizontal clearance between the nearer conductor and any part of such building 2.0 + (0.3 for every additional 33 KV )

Clearance above ground at the lowest conductor:

Voltage Description Distance
Low & Medium Voltage Across a street 5.8 Meter
High Voltage Across a street 6.1 Meter
Low & Medium Voltage Along a street 5.5 Meter
High Voltage Along a street 5.8 Meter
Low & Medium Voltage Elsewhere than along or across any street 4.0 Meter
High Voltage Elsewhere than along or across any street 5.2 Meter
33 KV & EHV Clearance above ground (Add 0.3 Meter for every 33 KV Volts in 5.2 Meter) Min 6.1 Meter

Vertical Clearance at Middle of Span:

Span

Vertical Clearance (At Middle of Span)

200 Meter

4.0 Meter

300 Meter

5.5 Meter

400 Meter

7.0 Meter

500 Meter

8.5 Meter

Safety Clearance from Live Part in Outdoor Substation:

KV

Safety Working Clearance

12 KV

2.6 Meter

36 KV

2.8 Meter

72.5 KV

3.1 Meter

145 KV

3.7 Meter

220 KV

4.3 Meter

400KV

6.4 Meter

800 KV

10.3 Meter

Lying of Telecommunication Cables with Power Cables (>33 kV).

Cable

Min. Distance

Power cable of voltage exceeding 33 kV shall be laid

Min 1.2 Meter depth

Underground telecommunication cable shall be with underground power cable of voltage exceeding 33 kV.

Min 0.6 Meter Separate from Power Cable

Safe approach limits for people :

Voltage

214V to 415 KV

11KV

33KV

66KV

132KV

275KV

Person using manually operated tool 1.3 Meter 2.0 Meter 3.0 Meter 4.0 Meter 5.0 Meter 6.0 Meter
Person using power operated tool 3.0 Meter 3.0 Meter 3.0 Meter 4.0 Meter 5.0 Meter 6.0 Meter

About Jignesh.Parmar (B.E,Mtech,MIE,FIE,CEng)
Jignesh Parmar has completed M.Tech (Power System Control), B.E(Electrical). He is member of Institution of Engineers (MIE) and CEng,India. Membership No:M-1473586.He has more than 16 years experience in Transmission -Distribution-Electrical Energy theft detection-Electrical Maintenance-Electrical Projects (Planning-Designing-Technical Review-coordination -Execution). He is Presently associate with one of the leading business group as a Deputy Manager at Ahmedabad,India. He has published numbers of Technical Articles in "Electrical Mirror", "Electrical India", "Lighting India","Smart Energy", "Industrial Electrix"(Australian Power Publications) Magazines. He is Freelancer Programmer of Advance Excel and design useful Excel base Electrical Programs as per IS, NEC, IEC,IEEE codes. He is Technical Blogger and Familiar with English, Hindi, Gujarati, French languages. He wants to Share his experience & Knowledge and help technical enthusiasts to find suitable solutions and updating themselves on various Engineering Topics.